In accordance with the developing economy and growing population, an increasing number of tall buildings have been constructed over the last 20 years. In 2017, there were 144 new buildings worldwide that were 200 m or greater in height; 50% of these buildings were in China. Due to the vertical gradient impact of meteorological parameters, the energy performance of tall buildings differs from that of general buildings. Few studies exist on vertical meteorological changes using measured data at different heights. Most studies on dynamic energy simulation simulate meteorological parameters using models. This study explores vertical meteorological patterns using hourly dry-bulb temperature, relative humidity, and wind speed data from 2007 to 2017 for a 325 m meteorological tower in Beijing. The temperature decreased significantly with increasing altitude (~0.9 °C per 100 m), while the daily temperature difference decreased with increasing altitude. The absolute humidity did not change significantly with height. The wind speed increased with altitude at approximately 2 m/s per 100 m. The building simulation showed that the annual heating load at a height of 320 m increased by 85% from that at 8 m; the annual cooling load decreased by 20%. Such significant differences in thermal loads for 300-m-tall buildings confirm the need to consider vertical meteorological differences in building performance simulations for tall buildings. A greater number of measurement points at different heights improve the simulation accuracy. Guidance on selecting the heights for vertical metrological measurements is provided based on the influences of building thermal loads.