- Main
Room surface convective heat transfer with ceiling fans and its effect on radiant cooling systems
Published Web Location
https://doi.org/10.1080/19401493.2026.2656928Abstract
The integration of ceiling fans with radiant systems remains underexplored despite their potential to address cooling capacity limitations. This study adopts a two-step approach to quantify the impact of elevated air movement on thermally activated building systems (TABS). First, we used OpenFOAM to calculate convective heat transfer coefficients under varying airflows, air-to-surface temperature differences, and zone sizes. These coefficients also apply to ceiling fans in buildings without radiant systems. Second, we implemented these coefficients in EnergyPlus to evaluate key radiant design parameters. Scenario 1 results show median steady-state cooling heat transfer rates increase of up to 47% relative to the no-fan cases when operative temperature is held constant. Scenario 2 demonstrates a median cooling effect of up to 4.8 K under fixed capacity, reflecting both lower zone temperatures and direct air movement on occupants. Overall, TABS-fans systems offer a scalable strategy to enhance comfort, increase capacity, and reduce energy demand.